⊙ Characteristic
. Adopting double safety circuit so that the system is not to be operated
when there is an abnormal signal on the flame detection circuit
. Safety system operates when a fire is not ignited or a fire goes out
suddenly
. Removes inflammable gas in the furnace when there is a fire extinction
or an operating interruption
. In preparation of fire extinction, manually reset is operated
⊙ Nominal
. Nominal voltage : AC 200~240V 50/60㎐ 1phase
. Ambient temperature : -20℃ ~ 60℃
. Ambient air density : 35% ~ 85%
. Power capacity : AC250V 5A
. Power consumption : < MAX 7W , AC 30mA
⊙ Time
. Pre purge time : 15S ± 4S
. Post ignition time : 6S ± 2S
. Safety switch : 3S ± 1S
. Delay in extinction detection : less than 1S
. Post purge (incase of Safety switch ) : 20S ± 5S
⊙ Fire detection (FLAME ROD/UV rectification type)
. Ignition detection current : >DC 2㎂
. Misfiring current : <DC 0.7㎂
⊙ Circuit connection